Enquire about "Cat Switchgear" Now
Switchgear and Paralleling Controls
Cat Switchgear
Cat Switchgear
- Independently certified to meet IEC 61439-2:2011 BS & international standard.
- Standard ACB breaker range 1600A
- 4000A CE & EAC marked. - Standard breaker fault rating 65 kA Icc, option for 100kA Icc ABB Emax 2 E4.
- Certified assembly high fault rating, tested up to 100 kA / 1s ICW
- Certified standard temperature rise tested.
- Design verification to Annex D of IEC 61439-2:2011
- Smaller footprint matched to the generator packaged design.
- Innovative cableway management.
- Modularity:
- Built around 150mm modules in 3 axis.
- Framework utilises a 25mm grid allowing a fully configurable system.
- Easy to extend and upgrade.
- Copper HDHC:
- Standard 10mm copper with 10mm spacing improves heat rejection.
- Stainless steel mounted busbar supports, reduce eddy currents.
- Fully tinned option.
- Breaker options:
- Accommodates fixed or withdrawable breakers.
- 3 or 4 pole option.
- Manual or motorized option.
- ACB door selection option.
- Enclosure options: o Options up to Form 4b separation.
- Configurable for top or bottom entry.
- Swivel lifting eye (4 point lift) for single sections.
- IP54 protection option.
- 50 °C option.
- Option to include generator controllers or PLC.
- EPD white powder coated, option for custom colours.
- In house automated routine testing.
- Rating plate.
- Cat warranty.
Enclosure Rating | |
---|---|
Configuration | IP4X |
Operating Temperature | |
---|---|
Operating Temperature | 35 u00b0C / 40 u00b0C @ 1 hr, option for 0u202650 u00b0C (32u2026122 u00b0F) |
Dimensions | |
---|---|
Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. |
Technical Summary | |
---|---|
Technical Summary | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. |
Application | |
---|---|
Application | LV 380u2026480 VAC, 50 Hz, 3-Phase. |
Modes of Operation | |
---|---|
Modes of Operation | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. |
Dimensions | |
---|---|
Standard Heights | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping |
Standard Depths | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers |