XQC1200

  • Overview
  • View product Download
CALCULATE FINANCE

Rental Ready

Extensive range of rental ready features to meet job requirements and applications.

Fuel/Emissions Strategy

Low BSFC and Low Emissions* ratings, switchable via Cat Electronic Technician (ET)
* Does not conform to EPA/EU emissions standards

Reliable, Fuel Efficient Cat Diesel Engine

The compact, four-cycle Cat 3512C turbocharged-aftercooled (SCAC) diesel engine provides proven durability and dependability
Best-in-class fuel economy
Fuel system operates on a variety of fuels
50/60 Hz switchable with neither software re-flashing, nor iron changes required
Other engine features include: electric fuel priming, individual cylinder temperature monitoring, and extended filter change intervals

Cat EMCP Control Panel

EMCP 4.3 control panel offers engine and generator monitoring and protection
On-Package Auto Paralleling Controls
AGC-4 provides paralleling, load sharing, VFD control, and additional generator protection

Cat Generator

Cat SR500 generator designed to match the performance and output characteristics of the Cat Gas engine.
Class H insulation operating at Class F temperature for extended life
Coastal insulation protection and anti-condensation space heaters
Integrated Voltage Regulator (IVR) for fast response in demanding applications

Cooling System

Provides 40°C (104F) ambient capability at 50 Hz, or 42°C (108F) capability at 60 Hz
at the IPP Rating at 750m (2,460 ft) above sea level
Variable frequency fan drive with smart fan control
Energy efficient electric drive fans

Sound Attenuated Container

Meets 83 dB(A) (50 Hz) / 85 dBA (60 Hz) at 7m (23 ft)
20′ ISO high cube container, 9-high stack CSC certified
Service and Personnel doors
Externally-accessible controls

Cat Connect

Remote monitoring for fleet management and asset tracking.

Reduced Environmental Impact

110% spill containment of onboard engine fluids
Positive crankcase fumes ventilation

Single-Source Supplier

Generator set manufactured in ISO 9001:2000 compliant facility
Package factory designed and production tested

Worldwide Product Support

Cat® dealers provide extensive post sale support including maintenance and repair agreements.
Supported 100% by the Cat dealer with warranty on parts and labor.
Extended Service Coverage (ESC) options available for coverage beyond the Standard Warranty period

Generator Set
Rating 1150kW (1438 kVA) Continuous
Frequency 50/60 Hz
Voltage 230 - 480 V
IPP Overload 50Hz 1205 ekW (1506 kVA)
Engine
Engine Cat 3512C
Fuel Diesel
Dimensions
Weight - Without Chassis, With Fuel, Lube Oil and Coolant 21518 kg (47440 lb)
Width - Without Chassis 2438 mm (97.5 in)
Height - Without Chassis 2896 mm (114 in)
Length - Without Chassis 6100 mm (240 in)
Generator Set
IPP Rated 60Hz 1260 ekW (1575 kVA)
IPP Overload 60Hz 1330kW; (1662KVA)

Standard Equipment

  • Cat 3512C heavy duty diesel engine
    • Heavy duty, dual element, PowerCore air cleaners with service indicators
    • Secondary fuel filters
    • Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil
    • Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
    • Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
    • Fuel cooler and electric priming pump
    • Electronic differential pressure monitoring of all filters
    • Electronic ADEM™ A4 engine controls
    • 24V electric starting motor
  • SR5 Generator
    • Double-bearing, SR-5 generator with anti-condensation space heaters (1.2 kW, 480VAC)
    • Brushless, random-wound, permanent magnet excited, thouree-phase, 4-lead design
    • Class H insulation operating at Class F temperature for extended life
    • Cat Integrated Voltage Regulator (Cat IVR)
    • Stator winding and bearing temperature sensors and RTD module
    • Metallic mesh generator air inlet filters (washable) with differential pressure monitoring
    • Coastal Insulation Protection
  • 20′ ISO high-cube container, 9-High stackable, CSC certified
    • Hinged, radiator air intake louvers
    • Sound-attenuated engine room air intake louvers with foldable awnings that double as shipping covers
    • Two (2) lockable personnel doors with panic releases
    • Interior walls and ceilings insulated with 50 mm of acoustic paneling
    • Side bus bar access door with external access load cable connections
    • Shore power via distribution block connections for jacket water heater, battery charger, and generator Anti-condensation Heaters
    • Four (4) DC lights with 60-min timer
    • Single-wall, 378-L (100gal) fuel tank; certified to BS799-5
    • Solenoid fuel-fill control valve for automated tank filling
    • Triple, primary fuel filters with integral water separators and service valves for on-the-fly changes
    • Sound attenuated to 83 dBA (50 Hz) / 85 dBA (60 Hz) at 7m (23 ft)
    • Two (2) 1400-CCA, Group 4D, maintenance-free batteries and 50-Amp battery charger
    • Insulated exhaust silencer with 1.8m (6ft) stainless steel exhaust stack for increased site power density
    • Engine vibration isolators
    • Easy drain access to standard fluids
    • Standard Cat decals and painted Cat Power Module White
  • Cooling
    • Cooling package provides 40°C (104F) ambient capability at 50 Hz, or 42°C (108F) capability at 60 Hz at the IPP Rating at 750m (2,460 ft) above sea level
    • Vertical, non-stacked radiator cores with dimpled fins and vertical air discharge
    • Variable frequency fan drive with smart fan control
    • Cat Extended Life Coolant (ELC)
  • Generator Controls and Protection
    • EMCP 4.3 generator set mounted controller
    • Automatic start/stop with cool down timer
    • Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
    • AGC-4 provides voltage and frequency adjust, base load / PF / load sharing / synchouronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level Indications & alarms, and fuel tank fuel transfer control
    • Reverse compatibility for interface to legacy power modules
    • 100 kAIC, 4000A-Frame generator circuit breaker with LSIG trip unit
    • Multi-mode operation: Island (kW/kVAR sharing), Base load power, Power management with multiple units
    • Manual and automatic paralleling capability
    • Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchouroscope
  • Quality
    • Factory testing of complete power module
    • CE Certified, NEMA, ISO and IEEE standards
    • O&M manuals

Enquiry Form

    REQUEST A CALL BACK
    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.