360°Exterior View

G3512 750kW Gas Generator Set

CALCULATE FINANCE

Emissions

One Safe Source

World Wide Product Support

SR5 Generator

  • Designed to match performance and output characteristics of Caterpillar gas engines
  • Industry leading mechanical and electrical design
  • High efficiency

EMCP 4.2 Control Panel

Proven System

CAT G3512 Gas Engine

CAT Electronic Control System

Generator Set Specifications
Gas Standby Rating 750 ekW @ 0.8pf
Fuel Type Natural Gas
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset
RPM 1800 rpm
Frequency 60 Hz
Engine Specifications
Engine Model G3512
Aspiration TA
Bore 170 mm (6.7 in)
Stroke 190 mm (7.5 in)
Generator Set Dimensions
Length 5224 mm (205.7 in)
Width 2286 mm (90 in)
Height 2525 mm (99.4 in)
Weight 12500 kg (27500 lb)
Engine Specifications
Governor Type ADEM A4

Standard Equipment

  • Air Inlet
    • Dual air cleaners, 1 per side, with service indicator
    • Two-element single-stage air cleaner with enclosure and service indicator
  • Control Panel
    • EMCP 4.3
  • Cooling
    • Engine driven pumps for jacket water and separate circuit aftercooler
    • Jacket water and SCAC engine-driven pumps
    • Jacket water and SCAC thermostats
    • LH or RG connections when radiator is not selected
    • Package mounted radiator
  • Fuel
    • NOx sensor based air-fuel-ratio control
    • 0.5 to 5 psi engine fuel inlet pressure
    • Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
    • Gas Train: NFPA37 and CSA B149.3
  • Exhaust
    • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
    • Dry exhaust manifolds, insulated and shielded
    • Cat-flanged face outlet on turbocharger
  • Fuel System
    • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
    • Throttle plate, 24V DC actuator, controlled by GECM
    • Engine-installed electronic control valve
    • Gas pressure regulator
    • 24V DC energized-to-run (ETR) gas shutoff valve
  • General
    • Crankshaft vibration damper and guard
    • “Stationary Use Only” Label in Correspondence with EPA Nonroad Mobile SI rule 
    • Operation and maintenance manuals
    • Parts book
    • Paint- Caterpillar Yellow except rails and radiators gloss black 
    • RH Service
  • Lubrication
    • Gear type lube oil pump
    • Cartridge style oil filter
  • Generator
    • Anti-condensation space heater
    • Winding temperature detectors
    • NEMA Class H insulation
    • SR5
    • Permanent Magnet Excitiation
    • Caterpillar’s Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
  • Governing System
    • ADEM A4
  • Ignition System
    • Individual Cylinder Detonation Sensitive Timing (DST) 
    • Electronic Ignition System (controlled by ADEM A4) 
  • Governing
    • ADEM A4 speed governor with 4 to 20ma (0V to 5V) speed input
  • Starting/Charging
    • 24V DC starting motors
    • Batteries with rack and cables
    • Electric Starter

Optional Equipment

  • Air Inlet
    • Mounting brackets and piping
    • Air cleaner with precleaner
  • Circuit Breakers
    • S LSI, G LSIG, P LSIG-P, 4th Digit Type
    • Right, left, rear mounted
    • 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
    • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
    • 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
    • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
    • 3-pole (IEC 947-2 rated)
    • Frame mounting
  • Control Panel
    • Remote annunciator
    • Local alarm module
    • Local PC monitoring
    • Engine failure relay
    • Remote PC monitoring
  • Cooling
    • Coolant level drain line with valves, fan with guard
    • Remote radiator for JW and SCAC circuits, level switch included but not wired
    • Inlet/Outlet connections
  • Exhaust
    • 305 mm (12in.) elbow
    • 18, 25 dBA Attenuation
    • Flexible fittings
    • 305 mm (12 in.) muffler
    • 305mm (12 in) spark arresting muffler
    • 305 mm (12 in.) flange
  • Fuel System
    • 3, 0-100 kPag, 4-20mA gas train pressure sensors
  • General
    • Special paint order
    • US AID emblem
    • Tool set
    • Digital diagnostic tool
  • Generator
    • Cable access box
    • Generator air filter
    • European bus bars
    • Low voltage extension box
    • Bearing temperature detectors
  • Starting/Charging
    • 20A, 24VDC battery charger
    • 24V starting motors
    • Battery with cables and rack (shipped ;ppse_
    • Jacket water heater
    • 45A, 24V charging alternator (requires engine driven pumps)