3516B (50 Hz) India Market Only

  • Overview
  • View product Download

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
  • Cat EMCP Control Panel

    The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

    Design Criteria

    The generator set meets transient response and block loading steps as per ISO 8528-5.

    Single-Source Supplier

    Fully prototype tested with certified torsional vibration analysis available

    World Wide Product Support

    Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

    Generator Set Specifications
    Minimum Rating 2000 kVA
    Maximum Rating 2000 kVA
    Voltage Voltage - Low (415 Volts), Medium and High Voltage
    Frequency 50 Hz
    Speed 1500 RPM
    Generator Set Configurations
    Emissions/Fuel Strategy Low Fuel Consumption
    Engine Specifications
    Engine Model 3516B TA, V-16, 4-Stroke Water-Cooled Diesel
    Bore 170 mm (6.69 in)
    Displacement 69 L (4210.64 inu00b3)
    Stroke 190 mm (7.48 in)
    Compression Ratio 14.0:1
    Aspiration TA
    Governor Type Adem™3
    Fuel System Electronic unit injection

    Standard Equipment

    • Air Cleaner
      • Cooling
        • Radiator or heat exchanger
      • Generator
        • Control Panel
          • EMCP 4.2 Controller
        • Muffler
          • Battery
            • Circuit Breaker

              Optional Equipment

              • Air starting motor with control and silencer
              • Jacket water Heater
              • Barring tool Device
              • Remote mounted Radiator
              • Air Inlet shutoff
              • Duplex Fuel Filter
              • Heavy -duty air cleaner
              • Option for remote mounting of UIP
              • Over size Generator
              • Electric Pre lub pump
              • Duplex oil Filter

              Enquiry Form

              REQUEST A CALL BACK