3512B (50 Hz) India Market Only

Design Criteria

The generator set meets transient response and block loading steps as ISO 8528-5.

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets other NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
  • Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
  • EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
  • Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
  • One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
  • World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
  • Generator Set Specifications
    Minimum Rating 1500 kVA
    Maximum Rating 1500 kVA
    Emissions/Fuel Strategy Low Fuel Consumption
    Voltage Low (415 Volts), Medium and High Voltage
    Frequency 50 Hz
    Speed 1500 rpm
    Duty Cycle Standby, Prime
    Engine Specifications
    Engine Model 3512B TA, V-12, 4-Stroke Water-Cooled Diesel
    Bore 170 mm (6.69 in)
    Stroke 190 mm (7.48 in)
    Displacement 51.8 l (3161.03 inu00b3)
    Compression Ratio 14.0:1
    Aspiration TA
    Fuel System Electronic Unit Injection
    Governor Type Adem™3
    Generator Set Dimensions
    Length - Maximum 5249 mm (206.6 in)
    Width - Maximum 197 mm (77.8 in)
    Height - Maximum 2367 mm (93.2 in)

    Standard Equipment

    • Cooling System
      • Radiator or heat exchanger
    • Control Panel
      • EMCP 4.2
    • General
      • Paint – Caterpillar Yellow except rails and radiators gloss black

    Enquiry Form