360°Exterior View

3516C (50 Hz) with Upgradeable Package

CALCULATE FINANCE

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • IBC Seismic Certification
  • EU Certification of Conformance (CE)
  • EEC Declaration of Conformity

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Generator Set Specifications
Minimum Rating 2500 kVA
Maximum Rating 2750 kVA
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 380 to 11000 volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Standby, Mission Critical, Prime
Engine Specifications
Engine Model 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
Bore 170 mm (6.69 in)
Stroke 215 mm (8.46 in)
Displacement 78 l (4765 in)
Compression Ratio 14:01
Aspiration TA
Fuel System Electronic unit injection
Governor Type Adem™3
Generator Set Dimensions
Length - Maximum 5800 mm (228.3 in)
Width - Maximum 1929 mm (75.9 in)
Height - Maximum 2050 mm (80.7 in)
Dry Weight - Genset (maximum) 14698 kg (32404 lb)

Standard Equipment

  • Air Inlet System
    • Air cleaner
    • Single element canister type with service indicator
  • Air Inlet
    • Air Cleaner
  • Control Panel
    • 2 programmable relay outputs (Form C)
    • Low coolant temperature
    • Speed adjust
    • Overspeed
    • Volts (L-L & L-N)
    • 4 programmable relay outputs (Form A)
    • Low oil pressure
    • Generator phase sequence
    • EMCP 4 Genset Controller
    • Communications:
    • Generator mounted – rear facing
    • Warning/shutdown with common LED indication of shutdowns for:
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • Reverse reactive power (kVAr) (32RV)
    • kW (per phase, average & percent)
    • Amps (per phase & average)
    • RPM
    • Engine cool-down timer
    • DC volts
    • Text alarm / event descriptions
    • 24-volt DC operation
    • Reverse power (kW) (32)
    • Alarm acknowledge
    • kW-hr (total)
    • 2 programmable digital outputs
    • Lamp test
    • Engine cycle crank
    • 6 programmable digital inputs
    • Programmable protective relaying functions:
    • Emergency stop
    • Overcurrent (50/51)
    • Emergency stop pushbutton
    • Failure to start (overcrank)
    • Operating hours
    • Coolant temperature
    • kVAr-hr (total)
    • Accessory module data link
    • Over / under frequency (81 o/u)
    • kVA (per phase, average & percent)
    • Over / under voltage (27/59)
    • Controls:
    • kVAr (per phase, average & percent)
    • Low coolant level
    • EMCP4.2 controller includes:
    • Serial annunciator module data link
    • Customer data link (Modbus RTU)
    • Oil pressure (psi, kPa or bar)
    • Digital indication for:
    • Panel lights
    • EMCP 4.2
    • Environmental sealed front face
    • Power Factor (per phase & average)
    • Frequency (Hz)
    • High coolant temperature
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Primary fuel filter with integral water separator
    • Fuel priming pump
    • Secondary fuel filter
  • Generator
    • IP23 Protection
    • Matched to the performance and output characteristics of Cat engines
  • Power Termination
    • Bus Bar
  • Starting/Charging
    • Heavy-duty starting system
    • Charging alternator
  • Cooling System
    • Coolant level sensors
    • Caterpillar Extended Life Coolant
    • Fan and belt guards
    • Coolant drain line with valve
    • Radiator fan and fan drive
    • JWAC
  • Cooling
    • Package mounted radiator
  • Exhaust System
    • Dry exhaust manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Fuel cooler; not included with packages without radiator
    • Secondary fuel filters
    • Flexible fuel lines – shipped loose
    • Fuel priming pump
  • Generators and Attachments
    • IEC standard hole pattern
    • NEMA Class H insulation, Class H temperature rise at 40C ambient
      (125C prime / 150C standby).
    • Bus bar connections, top center mounted, top cable entry
    • Generator set packages include Caterpillar’s Digital Voltage Regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
    • Internal excitation
    • 3 phase brushless, salient pole
    • Winding temperature detectors
    • Random wound
    • 6 lead
  • Governing System
    • ADEM III
  • Literature
    • English
  • Lube System
    • Fumes disposal
    • Oil drain lines and valve
    • Lubricating oil
    • Gear type lube oil pump
    • Oil filter, filler and dipstick
    • Integral lube oil cooler
  • Mounting System
    • Rails – engine / generator / radiator mounting
    • Rubber anti-vibration mounts (shipped loose)
  • Starting / Charging System
    • Battery disconnect switch
    • Battery and battery rack w/cables
    • 24 Volt electric starting motor
  • General
    • Paint: Caterpillar yellow with high gloss black rails & radiator
    • Right hand servicing
    • Paint – Caterpillar Yellow except rails and radiators gloss black
    • Flywheel and flywheel housing-SAE No. 00
    • SAE standard rotation

Optional Equipment

  • Air Inlet System
    • Heavy duty air cleaners
    • Air inlet protection
    • Dual element air cleaners
    • Remote air inlet adapters
  • Circuit Breakers
    • Cable entry options
    • Trip Units
    • EMAX breakers
    • Center posts busbars
    • Load take off; IEC standard hole
    • Optional busbar power connections
    • Control packaging for enclosures
  • Power Termination
    • Circuit breakers, IEC compliant
  • Control Panels
    • Vandal proof panel door
    • EMAX breaker connections
    • Language options
    • Annunciator modules
    • Remote speed adjust
    • Governors
    • External box clips
    • EMCP 4.3, EMCP 4.4
    • Local and remote monitoring
    • Auxiliary box
    • Voltage raise / lower switch
    • Customer interface options
    • Busbar connections
    • Generator temperature monitoring
  • Cooling System
    • Radiator duct flanges
    • Heat exchangers
    • Water level switch gauges
    • Optional Serpentine radiators
  • European Certifications
    • EU declaration of conformity
  • Exhaust System
    • Mufflers
    • Through wall installation kit
    • Muffler mounting kits
    • Flexible fittings
  • Fuel System
    • Fuel coolers
    • Primary fuel filter
  • Generators and attachments
    • Number of leads: 6
    • 3 Phase, Random wound, Internal excitation
    • Pitch: 0.6667
    • Internal excitation
    • Random wound
    • Optional generators
    • 3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
       
  • Instrumentation
    • Pyrometers and thermocouples
    • Thermocouples
  • Lube System
    • Oil level regulator
    • Manual prelube sump pumps
    • Electric prelube pumps
  • Mounting System
    • IBC vibration isolators
    • Spring type vibration isolators
  • Protection System
    • Explosion relief valves
  • Special Tests / Reports
    • PGS test report @ 0.8 power factor
    • PGS test report @ 1.0 power factor
    • CSA test and certification
    • IBC seismic certificate
    • Neutral ground certificate
  • Starting / Charging System
    • Charging alternators – 50 Amp
    • ETHER starting aids
    • 10 and 20 amp battery chargers
    • Dual 24 volt electric starting motors
    • 24 Volt battery sets – Dry
    • Jacket water heaters
  • General
    • Engine barring group

Enquiry Form

REQUEST A CALL BACK